Task 1 - IP Address via RSLinx
Equipment Needed
- RSLinx Classic
- Ethernet Cable
- (Optional) USB Cable
Assumptions
The Ethernet procedure assumes that the device is being assigned an IP address by a DHCP server. Henry Pump shop computers are configured with a DHCP server to assign IP addresses on the 192.168.1.0 network.
Procedure (Ethernet)
- Ensure your PC IP Address is a member of the same subnet as the device.
- Open RSLinx Classic
- If there is already an EtherNet\IP Devices driver setup, skip to step 9.
- Click the “Configure Drivers” button or navigate to “Communications > Configure Drivers”.
- Under “Available Driver Types” select “EtherNet\IP Devices” and click “Add New…”
- Choose a name for the driver or leave it as the default.
- Select which network port to use for the driver. This is typically “Windows Default” or the Ethernet Port.
- Close the “Configure Drivers” window.
- Click the RSWho button or navigate to “Communications > RSWho”.
- Expand the EtherNet\IP Devices driver to begin browsing the network.
- Locate the device in the browse list.
- Right-click on the device and select “Module Configuration”.
- In the “Port Configuration” Tab, select to “Manually configure IP settings” and input the desired IP settings. Click OK.
- Verify in the browse list that the device is now using the correct IP Address.
Procedure (USB)
- Open RSLinx Classic
- Expand the USB driver to begin browsing the network.
- Locate the device in the browse list.
- Right-click on the device and select “Module Configuration”.
- In the “Port Configuration” Tab, select to “Manually configure IP settings” and input the desired IP settings. Click OK.
- Connect an ethernet cable from the PC to the device and ensure that the PC has an IP Address on the same subnet as the device.
- If there is already an EtherNet\IP Devices driver setup, skip to step 9.
- Click the “Configure Drivers” button or navigate to “Communications > Configure Drivers”.
- Under “Available Driver Types” select “EtherNet\IP Devices” and click “Add New…”
- Choose a name for the driver or leave it as the default.
- Select which network port to use for the driver. This is typically “Windows Default” or the Ethernet Port.
- Close the “Configure Drivers” window.
- Click the RSWho button or navigate to “Communications > RSWho”.
- Expand the EtherNet\IP Devices driver to begin browsing the network.
- Verify in the browse list that the device is now using the correct IP Address.